Example filled in: a 3PL building with 12 forklift batteries, a diesel generator tank and propane cylinders. Enter the largest amount on site on any one day last year.
| Chemical | Tier II threshold | Max on site | Unit | Specific gravity, if gallons | Result |
|---|---|---|---|---|---|
| Sulfuric acid (battery acid, all batteries) EHS. Threshold planning quantity 1,000 lb | 500 lb | 0 | |||
| Lead acid batteries, total weight (EPA option for lead) Not an EHS. Or add up lead itself | 10,000 lb | 0 | |||
| Diesel fuel (generator, fire pump, yard fueling) Not an EHS | 10,000 lb | 0 | |||
| Propane (forklift cylinders and tanks) Not an EHS | 10,000 lb | 0 | |||
| Anhydrous ammonia (refrigeration) EHS. Threshold planning quantity 500 lb | 500 lb | 0 | |||
| Gasoline Not an EHS. The 75,000 gal figure applies only to retail gas stations | 10,000 lb | 0 | |||
| Any other hazardous chemical with an SDS Not an EHS | 10,000 lb | 0 |
Checking
Extremely hazardous substances (EHS): report at 500 lb or the threshold planning quantity, whichever is lower: 40 CFR 370.10(a)(1).
All other hazardous chemicals: report at 10,000 lb: 40 CFR 370.10(a)(2)(i).
Gallons to pounds = gallons × specific gravity × 8.3, the method used by TCEQ's Tier II weight converter. Specific gravity is on the SDS.
Section 302 notice: any EHS at or over its threshold planning quantity: 40 CFR 355.10 and 355.12.
The two thresholds that matter in a warehouse
Federal Tier II reporting has two main thresholds. A chemical on EPA's list of extremely hazardous substances is reportable at 500 lb or its threshold planning quantity, whichever is lower. Every other hazardous chemical that needs a safety data sheet under OSHA is reportable at 10,000 lb. The test is the largest amount present at any one time during the calendar year, not the yearly total that passed through the building.
| Chemical | EHS? | Threshold planning quantity | Tier II threshold | Where it shows up |
|---|---|---|---|---|
| Sulfuric acid, CAS 7664-93-9 | Yes | 1,000 lb | 500 lb | Lead acid forklift and floor scrubber batteries |
| Anhydrous ammonia, CAS 7664-41-7 | Yes | 500 lb | 500 lb | Cold storage refrigeration systems |
| Lead | No | None | 10,000 lb | Lead acid batteries |
| Diesel fuel | No | None | 10,000 lb | Generator and fire pump tanks, yard fueling |
| Propane | No | None | 10,000 lb | Forklift cylinders, bulk tanks |
| Gasoline | No | None | 10,000 lb | Fleet fueling. Retail stations have a separate 75,000 gal threshold |
Inventory you only store for customers still counts if it is a hazardous chemical present at the facility, unless an exemption in 40 CFR 370.13 applies, such as products in the same form and concentration as packaged for the general public. That exemption does not cover forklift batteries.
Gallons and pounds
Thresholds are in pounds. Tanks are measured in gallons. Multiply gallons by the specific gravity on the safety data sheet and by 8.3, the factor TCEQ's Tier II weight converter uses for the weight of a gallon of water. The example row uses a specific gravity of 0.85 for diesel only to show the math. Use the figure on your own SDS.
What the result means
If any row says Report, the facility owes a Tier II report for that chemical by March 1, filed in the state's system and sent to the state emergency response commission, the local emergency planning committee and the fire department. A state can set lower thresholds or add chemicals, so check your state's page as well.
If sulfuric acid or ammonia reaches its threshold planning quantity, the facility also owes a one-time emergency planning notice to the state commission and the local committee within 60 days under 40 CFR 355.20, and names a facility emergency coordinator.
Common questions
Is diesel in a generator tank reportable?
Yes, if the diesel on site reaches 10,000 lb at any one time. Include generator, fire pump and fueling tanks. The 100,000 gallon diesel figure in the rule applies only to retail gas stations with compliant underground tanks.
Do I add up propane cylinders?
Add the propane in every cylinder and tank on site to get the facility total, then compare it to 10,000 lb. EPA's mixture rule in 40 CFR 370.14 asks for the total quantity present throughout the facility.
Does inventory I store for a customer count?
It can. The rule covers hazardous chemicals present at the facility. Consumer packaged goods in the same form and concentration as sold to the public are exempt under 40 CFR 370.13.